Report No. 2: Soil and Core Test Results
RE: Analysis and Investigation of existing cracks on
floor slab inside the warehouse
Dear
Mrs. Orenstein:
Upon your request, Chaiban Engineering
Consultants, Inc. staff conducted field observations and inspections for
the referenced project referenced building on
Previous recommendation
were as follows:
On
Concrete
core tests:
|
Core # |
Core Diameter (in) |
Core thickness (in) |
Compressive strength test results (psi) |
Compressive strength required (psi) |
Reinforcement |
Comments |
|
1 |
3.75 |
4.25 |
2348 |
4000 |
none |
Fail |
|
2 |
3.75 |
4 |
2225 |
4000 |
none |
Fail |
Average strength: 2348+2225/2 = 2,286.5 psi
Notes:
1)* For core locations,
reference sketch attached
2) Plans indicated a thickness of 4 inches with wire
mesh reinforcement, 6x6~10-10
WWM and
compressive strength = 4000 psi @ 28 days.
3) Reinforcement : Based on
core tests, no reinforcement was found.
Soil Boring Tests:
Depth Soil Description
0’-0” -
0’-5”
Concrete
0’-5” - 1’-0” Pale Brown sand
w/rock
1’-0” - 5’-6” White sand
5’-6” - 8’-0” Very pale brown sand
8’-0” - 10’-0” Lime rock
* For boring locations, reference sketch attached
Analysis &
investigations:
Based
on the concrete core test results above, the compressive strength of the concrete averaged
about 2,286.5 psi. However the minimum recommendation of the compressive
concrete strength is 4000 psi in accordance with Florida building code 2001
section 1904 table 1904D. Additionally, there is no evidence that reinforcement
bars or reinforcement wire exist or present in the slab. Based on our past
experience, reinforcement is required in 4” thick concrete slabs. Additionally, the soil boring
results indicated that the existing soil condition can reach allowable bearing capacity of 2500 psf.
Based
on soil test data, our opinion is that the soil classification did not reveal
any weak soils below the subject structure. The lab certified that the minimum
bearing capacity of the soil is 2,500 PSF.
Recommendations:
Upon our evaluation, we offer the
following recommendations :
Conclusion:
In conclusion,
our analysis and investigation of the concrete core test and soil boring
results indicated that existing floor slabs inside the storage area were
under-designed, due to insufficient concrete compressive strength averaging 2,286.5 psi. The minimum allowable concrete compressive strength
for slab bearing on the grade is 4,000 psi per Florida Building Code 2001 Section
1904 table 1904D. In addition, the concrete core sample did not reveal any
reinforcement such as rebar or welded wire reinforcement fabric, which from our
past experience, is commonly used in structural slabs with thickness of 4” or larger.
At this time, we cannot determine if the existing steel pipe columns are
bearing on concrete footing or not. In the event, further inspections and
removal of existing slab reveal that no such footings exist, then, new
footings must be constructed in accordance with 2001 Florida Building Code.
We advise to proceed
immediately with the repairs or replacement as mentioned herein above, and attached specifications to repair the roof, wall
stucco, sealant, cracks along the ceiling and exterior wall cracks, replace the
floor slabs inside the storage room with new design by a certified structural
engineer, PE (CEC). All repairs to be performed based on approved sealed drawings and
a building permit issued by the local Building department.
We would be more
than happy to provide you with engineering design repair drawings and
specifications upon your request.
This report is
made on the basis of what was visible and accessible at the time of
inspections.
This inspection
and report does not constitute a guarantee that there are no other deficiencies
than those noted, or that additional problems will not occur in the future.
Further, our company and employees assumes no liability whatsoever as a result
of this inspection and report.
Please
note that the engineer present on site during repairs reserves the right to
recommend additional repairs upon visual observations.
We
reserve the right to amend this report should additional information be
presented.
Thank you for using our
services.
Respectfully Submitted,
Chaiban Engineering
Consultants, Inc.
Joseph B. Chaiban, P.E.,
Managing Partner
P. E. No. 43239
Special Inspector No. 1188
Certificate of Authorization
No. 7185